CVE-2019-10939

Published Apr 14, 2020

Last updated 6 months ago

Overview

Description
A vulnerability has been identified in TIM 3V-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3). The affected versions contain an open debug port that is available under certain specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2. If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.
Source
productcert@siemens.com
NVD status
Modified

Risk scores

CVSS 3.1

Type
Primary
Base score
9.8
Impact score
5.9
Exploitability score
3.9
Vector string
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Severity
CRITICAL

CVSS 2.0

Type
Primary
Base score
6.8
Impact score
6.4
Exploitability score
8.6
Vector string
AV:N/AC:M/Au:N/C:P/I:P/A:P

Weaknesses

productcert@siemens.com
CWE-489
nvd@nist.gov
NVD-CWE-Other

Social media

Hype score
Not currently trending

Configurations