ICS vulnerabilities

Showing 301 - 350 of 388 CVEs

  1. CVE-2022-3682 Published Mar 28, 2023

    A vulnerability exists in the SDM600 file permission validation. An attacker could exploit the vulnerability by gaining access to the system and uploading a specially crafted message to the system node, which could result in Arbitrary code Executing. This issue affects: All SDM600 versions prior to version 1.2 FP3 HF4 (Build Nr. 1.2.23000.291) List of CPEs: * cpe:2.3:a:hitachienergy:sdm600:1.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.9002.257:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.10002.257:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.11002.149:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.12002.222:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.13002.72:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.44:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.92:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.108:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.182:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.257:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.342:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.447:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.481:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.506:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.14002.566:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.20000.3174:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.21000.291:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.21000.931:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.21000.105:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:sdm600:1.2.23000.291:*:*:*:*:*:*:*

  2. CVE-2023-1256 Published Mar 16, 2023

    The listed versions of AVEVA Plant SCADA and AVEVA Telemetry Server are vulnerable to an improper authorization exploit which could allow an unauthenticated user to remotely read data, cause denial of service, and tamper with alarm states.

  3. CVE-2023-22424 Published Mar 6, 2023

    Use-after-free vulnerability exists in Kostac PLC Programming Software (Former name: Koyo PLC Programming Software) Version 1.6.9.0 and earlier. With the abnormal value given as the maximum number of columns for the PLC program, the process accesses the freed memory. As a result, opening a specially crafted project file may lead to information disclosure and/or arbitrary code execution.

  4. CVE-2023-22421 Published Mar 6, 2023

    Out-of-bounds read vulnerability exists in Kostac PLC Programming Software (Former name: Koyo PLC Programming Software) Version 1.6.9.0 and earlier. The insufficient buffer size for the PLC program instructions leads to out-of-bounds read. As a result, opening a specially crafted project file may lead to information disclosure and/or arbitrary code execution.

  5. CVE-2023-22419 Published Mar 6, 2023

    Out-of-bounds read vulnerability exists in Kostac PLC Programming Software (Former name: Koyo PLC Programming Software) Version 1.6.9.0 and earlier. When processing a comment block in stage information, the end of data cannot be verified and out-of-bounds read occurs. As a result, opening a specially crafted project file may lead to information disclosure and/or arbitrary code execution.

  6. CVE-2023-0457 Published Mar 3, 2023

    Plaintext Storage of a Password vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series, MELSEC iQ-R Series, MELSEC-Q Series and MELSEC-L Series allows a remote unauthenticated attacker to disclose plaintext credentials stored in project files and login into FTP server or Web server.

  7. CVE-2023-23296 Published Feb 23, 2023

    Korenix JetWave 4200 Series 1.3.0 and JetWave 3200 Series 1.6.0 are vulnerable to Denial of Service via /goform/formDefault.

  8. CVE-2023-23294 Published Feb 23, 2023

    Korenix JetWave 4200 Series 1.3.0 and JetWave 3000 Series 1.6.0 are vulnerable to Command Injection. An attacker can modify the file_name parameter to execute commands as root.

  9. CVE-2023-23295 Published Feb 23, 2023

    Korenix Jetwave 4200 Series 1.3.0 and JetWave 3000 Series 1.6.0 are vulnerable to Command Injection via /goform/formSysCmd. An attacker an modify the sysCmd parameter in order to execute commands as root.

  10. CVE-2023-0451 Published Jan 26, 2023

    Econolite EOS versions prior to 3.2.23 lack a password requirement for gaining “READONLY” access to log files and certain database and configuration files. One such file contains tables with MD5 hashes and usernames for all defined users in the control software, including administrators and technicians.

  11. CVE-2022-2948 Published Dec 7, 2022

    GE CIMPICITY versions 2022 and prior is vulnerable to a heap-based buffer overflow, which could allow an attacker to execute arbitrary code.

  12. CVE-2022-3270 Published Dec 1, 2022

    In multiple products by Festo a remote unauthenticated attacker could use functions of an undocumented protocol which could lead to a complete loss of confidentiality, integrity and availability.

  13. CVE-2022-40799 Published Nov 29, 2022

    Data Integrity Failure in 'Backup Config' in D-Link DNR-322L <= 2.60B15 allows an authenticated attacker to execute OS level commands on the device.

  14. CVE-2022-3181 Published Nov 2, 2022

    An Improper Input Validation vulnerability exists in Trihedral VTScada version 12.0.38 and prior. A specifically malformed HTTP request could cause the affected VTScada to crash. Both local area network (LAN)-only and internet facing systems are affected.

  15. CVE-2022-20775 Published Sep 30, 2022

    A vulnerability in the CLI of Cisco SD-WAN Software could allow an authenticated, local attacker to gain elevated privileges. This vulnerability is due to improper access controls on commands within the application CLI. An attacker could exploit this vulnerability by running a maliciously crafted command on the application CLI. A successful exploit could allow the attacker to execute arbitrary commands as the root user. Cisco has released software updates that address this vulnerability. There are no workarounds that address this vulnerability. https://sec.cloudapps.cisco.com/security/center/content/CiscoSecurityAdvisory/cisco-sa-sd-wan-priv-E6e8tEdF

  16. CVE-2022-37300 Published Sep 12, 2022

    A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).

  17. CVE-2020-16235 Published May 19, 2022

    Inadequate encryption may allow the credentials used by Emerson OpenEnterprise, up through version 3.3.5, to access field devices and external systems to be obtained.

  18. CVE-2022-1161 Published Apr 11, 2022

    An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.

  19. CVE-2020-25184 Published Mar 18, 2022

    Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.

  20. CVE-2020-25182 Published Mar 18, 2022

    Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.

  21. CVE-2020-25180 Published Mar 18, 2022

    Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.

  22. CVE-2020-16232 Published Mar 18, 2022

    In Yokogawa WideField3 R1.01 - R4.03, a buffer overflow could be caused when a user loads a maliciously crafted project file.

  23. CVE-2022-0492 Published Mar 3, 2022

    A vulnerability was found in the Linux kernel’s cgroup_release_agent_write in the kernel/cgroup/cgroup-v1.c function. This flaw, under certain circumstances, allows the use of the cgroups v1 release_agent feature to escalate privileges and bypass the namespace isolation unexpectedly.

  24. CVE-2022-25359 Published Feb 26, 2022

    On ICL ScadaFlex II SCADA Controller SC-1 and SC-2 1.03.07 devices, unauthenticated remote attackers can overwrite, delete, or create files.

  25. CVE-2022-23921 Published Feb 25, 2022

    Exploitation of this vulnerability may result in local privilege escalation and code execution. GE maintains exploitation of this vulnerability is only possible if the attacker has login access to a machine actively running CIMPLICITY, the CIMPLICITY server is not already running a project, and the server is licensed for multiple projects.

  26. CVE-2022-21798 Published Feb 25, 2022

    The affected product is vulnerable due to cleartext transmission of credentials seen in the CIMPLICITY network, which can be easily spoofed and used to log in to make operational changes to the system.

  27. CVE-2022-25182 Published Feb 15, 2022

    A sandbox bypass vulnerability in Jenkins Pipeline: Shared Groovy Libraries Plugin 552.vd9cc05b8a2e1 and earlier allows attackers with Item/Configure permission to execute arbitrary code on the Jenkins controller JVM using specially crafted library names if a global Pipeline library is already configured.

  28. CVE-2022-24316 Published Feb 9, 2022

    A CWE-665: Improper Initialization vulnerability exists that could cause information exposure when an attacker sends a specially crafted message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior)

  29. CVE-2020-7534 Published Feb 4, 2022

    A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists on the web server used, that could cause a leak of sensitive data or unauthorized actions on the web server during the time the user is logged in. Affected Products: Modicon M340 CPUs: BMXP34 (All Versions), Modicon Quantum CPUs with integrated Ethernet (Copro): 140CPU65 (All Versions), Modicon Premium CPUs with integrated Ethernet (Copro): TSXP57 (All Versions), Modicon M340 ethernet modules: (BMXNOC0401, BMXNOE01, BMXNOR0200H) (All Versions), Modicon Quantum and Premium factory cast communication modules: (140NOE77111, 140NOC78*00, TSXETY5103, TSXETY4103) (All Versions)

  30. CVE-2022-23130 Published Jan 21, 2022

    Buffer Over-read vulnerability in Mitsubishi Electric MC Works64 versions 4.00A to 4.04E, Mitsubishi Electric GENESIS64 versions 10.97 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 and prior, Mitsubishi Electric ICONICS Suite versions 10.97 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97 and prior, Mitsubishi Electric GENESIS32 versions 9.7 and prior, and Mitsubishi Electric Iconics Digital Solutions GENESIS32 versions 9.7 and prior allows an attacker to cause a DoS condition in the database server by getting a legitimate user to import a configuration file containing specially crafted stored procedures into GENESIS64, ICONICS Suite, MC Works64, or GENESIS32 and execute commands against the database from GENESIS64, ICONICS Suite, MC Works64, or GENESIS32.

  31. CVE-2022-23129 Published Jan 21, 2022

    Plaintext Storage of a Password vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS GENESIS64 versions 10.90 to 10.97 allows a local authenticated attacker to gain authentication information and to access the database illegally. This is because when configuration information of GridWorX, a database linkage function of GENESIS64 and MC Works64, is exported to a CSV file, the authentication information is saved in plaintext, and an attacker who can access this CSV file can gain the authentication information.

  32. CVE-2022-23128 Published Jan 21, 2022

    Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97 and ICONICS MobileHMI versions 10.95.3 to 10.97 allows a remote unauthenticated attacker to bypass the authentication of MC Works64, GENESIS64, Hyper Historian, AnalytiX and MobileHMI, and gain unauthorized access to the products, by sending specially crafted WebSocket packets to FrameWorX server, one of the functions of the products.

  33. CVE-2022-23127 Published Jan 21, 2022

    Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions 10.96.2 and prior allows a remote unauthenticated attacker to gain authentication information of an MC Works64 or MobileHMI and perform any operation using the acquired authentication information, by injecting a malicious script in the URL of a monitoring screen delivered from the MC Works64 server or MobileHMI server to an application for mobile devices and leading a legitimate user to access this URL.

  34. CVE-2021-44228 Published Dec 10, 2021

    Apache Log4j2 2.0-beta9 through 2.15.0 (excluding security releases 2.12.2, 2.12.3, and 2.3.1) JNDI features used in configuration, log messages, and parameters do not protect against attacker controlled LDAP and other JNDI related endpoints. An attacker who can control log messages or log message parameters can execute arbitrary code loaded from LDAP servers when message lookup substitution is enabled. From log4j 2.15.0, this behavior has been disabled by default. From version 2.16.0 (along with 2.12.2, 2.12.3, and 2.3.1), this functionality has been completely removed. Note that this vulnerability is specific to log4j-core and does not affect log4net, log4cxx, or other Apache Logging Services projects.

  35. CVE-2021-42707 Published Nov 22, 2021

    PLC Editor Versions 1.3.8 and prior is vulnerable to an out-of-bounds write while processing project files, which may allow an attacker to execute arbitrary code.

  36. CVE-2021-38406 Published Sep 17, 2021

    Delta Electronic DOPSoft 2 (Version 2.00.07 and prior) lacks proper validation of user-supplied data when parsing specific project files. This could result in multiple out-of-bounds write instances. An attacker could leverage this vulnerability to execute code in the context of the current process.

  37. CVE-2021-22937 Published Aug 16, 2021

    A vulnerability in Pulse Connect Secure before 9.1R12 could allow an authenticated administrator to perform a file write via a maliciously crafted archive uploaded in the administrator web interface.

  38. CVE-2021-26829 Published Jun 11, 2021

    OpenPLC ScadaBR through 0.9.1 on Linux and through 1.12.4 on Windows allows stored XSS via system_settings.shtm.

  39. CVE-2021-26828 Published Jun 11, 2021

    OpenPLC ScadaBR through 0.9.1 on Linux and through 1.12.4 on Windows allows remote authenticated users to upload and execute arbitrary JSP files via view_edit.shtm.

  40. CVE-2021-22900 Published May 27, 2021

    A vulnerability allowed multiple unrestricted uploads in Pulse Connect Secure before 9.1R11.4 that could lead to an authenticated administrator to perform a file write via a maliciously crafted archive upload in the administrator web interface.

  41. CVE-2021-22899 Published May 27, 2021

    A command injection vulnerability exists in Pulse Connect Secure before 9.1R11.4 allows a remote authenticated attacker to perform remote code execution via Windows Resource Profiles Feature

  42. CVE-2021-22894 Published May 27, 2021

    A buffer overflow vulnerability exists in Pulse Connect Secure before 9.1R11.4 allows a remote authenticated attacker to execute arbitrary code as the root user via maliciously crafted meeting room.

  43. CVE-2021-22893 Published Apr 23, 2021

    Pulse Connect Secure 9.0R3/9.1R1 and higher is vulnerable to an authentication bypass vulnerability exposed by the Windows File Share Browser and Pulse Secure Collaboration features of Pulse Connect Secure that can allow an unauthenticated user to perform remote arbitrary code execution on the Pulse Connect Secure gateway. This vulnerability has been exploited in the wild.

  44. CVE-2020-26997 Published Apr 22, 2021

    A vulnerability has been identified in Solid Edge SE2020 (All versions < SE2020MP13), Solid Edge SE2020 (All versions < SE2020MP14), Solid Edge SE2021 (All Versions < SE2021MP4). Affected applications lack proper validation of user-supplied data when parsing PAR files. This could lead to pointer dereferences of a value obtained from untrusted source. An attacker could leverage this vulnerability to execute code in the context of the current process. (ZDI-CAN-11919)

  45. CVE-2020-14516 Published Mar 18, 2021

    In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.

  46. CVE-2021-22681 Published Mar 3, 2021

    Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.

  47. CVE-2020-25161 Published Feb 23, 2021

    The WADashboard component of WebAccess/SCADA Versions 9.0 and prior may allow an attacker to control or influence a path used in an operation on the filesystem and remotely execute code as an administrator.

  48. CVE-2020-10048 Published Feb 9, 2021

    A vulnerability has been identified in SIMATIC PCS 7 (All versions), SIMATIC WinCC (All versions < V7.5 SP2). Due to an insecure password verification process, an attacker could bypass the password protection set on protected files, thus being granted access to the protected content, circumventing authentication.

  49. CVE-2020-28895 Published Feb 3, 2021

    In Wind River VxWorks, memory allocator has a possible overflow in calculating the memory block's size to be allocated by calloc(). As a result, the actual memory allocated is smaller than the buffer size specified by the arguments, leading to memory corruption.

  50. CVE-2020-28391 Published Jan 12, 2021

    A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (All versions < V5.2.5), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.5.0), SCALANCE X-200RNA switch family (All versions < V3.2.7). Devices create a new unique key upon factory reset, except when used with C-PLUG. When used with C-PLUG the devices use the hardcoded private RSA-key shipped with the firmware-image. An attacker could leverage this situation to a man-in-the-middle situation and decrypt previously captured traffic.